GA2-B1-22-625-11-DE [Carling Technologies]
Magnetic Circuit Breaker, 2 Pole(s), 25A, 240VAC, Din-rail Mount,;型号: | GA2-B1-22-625-11-DE |
厂家: | Carling Technologies |
描述: | Magnetic Circuit Breaker, 2 Pole(s), 25A, 240VAC, Din-rail Mount, 电路保护 |
文件: | 总10页 (文件大小:1599K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
G-
G-Se
riesSeries
DIN-RAIL CIRCUIT BREAKER
The G-Series hydraulic-magnetic circuit breaker insures maximum protection by integrating wiping contacts
for longevity; a common trip linkage between poles; a unique terminal bus connection system; and optional
integrated auxiliary switch. It is also suitable for reverse feed and provides finger safe terminals. This DIN rail
mount circuit breaker accommodates either a 35mm x 7.5mm, or a 35mm x 15mm symmetrical din rails.
G-Series DIN Rail Circuit Breaker:
UL 489 Listed: 1 to 3 poles; 1-50 Amps; 125 VDC, 240 VAC;
UL 1077 Recognized: 1 to 4 poles; 0.1-63 Amps; 80 VDC, 240 VAC/480VAC; cUL, TUV, CSA & CCC.
Resources:
Configure a Complete Part
Download CAD & Sales Drawing
Product Highlights:
•ꢀ DINꢀRailꢀMounting
•ꢀ ULꢀ489ꢀListed
Typical Applications:
•ꢀ RenewableꢀEnergy
•ꢀ Telecom
•ꢀ ULꢀ1077ꢀRecognized,ꢀcUL,ꢀTUV,ꢀCSAꢀ&ꢀCCCꢀ
•ꢀ WipingꢀContacts
•ꢀ ControlꢀPanels
•ꢀ IndustrialꢀAutomationꢀControls
•ꢀ CommonꢀTripꢀLinkageꢀBetweenꢀPoles
•ꢀ OptionalꢀIntegratedꢀAuxiliaryꢀSwitch
Carling Technologies, Inc.
60 Johnson Avenue, Plainville, CT 06062
Email: sales@carlingtech.com
Application Support: team2@carlingtech.com
Phone: 860.793.9281 Fax: 860.793.9231
www.carlingtech.com
|
G-Series Circuit Breaker - DIN Rail – Design Features
2
G-Series
DESIGN FEATURES
TERMINAL BARRIERS
Meet UL 489 Spacing Requirements
DIN RAIL
4.56 in
[115.87 mm]
MOUNTING
Snap on Back Panel
Rail Mounting for
either 35 x 7.5 mm
or 35 x 15 mm
2.167 in
[55.04 mm
OPTIONAL AUXILIARY SWITCH
DIN RAIL LOCK
Provides Breaker Status Indication
Secures Circuit Breaker to the DIN Rail
Auxiliary Switch with Internal Connector
Example Plugs:
Spring clamp terminals
Screw terminals
Screw terminals 45° angle
Internal connector
Dimensions in mm
Advantages:
Wire size solid wire
0.2 - 1.5 mm ꢀ
0.2 - 2.5 mm ꢀ
Wire size stranded wire
- Pre-wiring is possible
- Easy interchangeable
- Time saving solution
- Various connection methods
- Many different plugs
Wire size stranded wire with ferrule 0.25 - 1.5 mm ꢀ
Wire stripping length
10 mm
The auxiliary contact with internal connector can be used with Phoenix Combicon plugs. Phoenix item
number internal connector: 1753453. The circuit breaker is standard delivered without plugs.
*Manufacturer reserves the right to change product specification without prior notice.
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
|
3
G-Series Circuit Breaker - DIN Rail – General Specifications
Electrical Tables
Table A: Lists UL Recognized, CSA Accepted and TUV Certified capabilities as a Component Supplementary Protector.
G-SERIES TABLE A: COMPONENT SUPPLEMENTARY PROTECTORS
Voltage
Current Rating Short Circuit Capacity (Amps)
Circuit
Max
Rating
80
240
240
480
Minimum
Full Load
Amps
Without Backup Fuse
Application Codes
Configuration
Frequency Phase
Poles
UL/CSA
3000
3000
3000
1500
TUV
UL
CSA
DC
---
1
1
1
2
3
.1 - 63
.1 - 63
.1 - 63
.1 - 63
1500
1500
1500
TC1, OL1, U1 TC1, OL1, U1
TC1, OL1, U1 TC1, OL1, U1
TC1, OL1, U1 TC1, OL1, U1
50 / 60
50 / 60
50 / 60
Series
1
3
415V, 1000 TC1, OL1, U1 TC1, OL1, U1
Table B: Lists UL Listed (489) configuration and performance capabilities.
G-SERIES TABLE B: UL 489 LISTED BRANCH CIRCUIT BREAKERS
Interrupting Capacity
(Amps RMS)
Circuit
Voltage
Current Rating
Full Load Amps
1 - 50
Configuration
Max Rating Frequency Phase
Poles
80
DC
---
---
1
1
5000
5000
5000
5000
125
DC
2
1 - 50
120
50 / 60
50 / 60
1
1 - 50
Series
120 / 240
1
1 - 31
1 - 50
240
50 / 60
1
1
1 - 25
5000
1
One pole out of the three poles must be a neutral break.
Electrical
Mechanical
Maximum Voltage
AC: 240VAC (single pole),
Endurance
10,000 ON-OFF operations @ 6 per
minute; with rated current & voltage.
All G-Series circuit breakers will
trip on overload, even when actuator
is forcibly held in the ON position.
The operating actuator moves
480VAC (3 poles, additional pole
shall be dedicated for neutral break)
DC: 80VDC (single pole & multipole)
0.1 – 63A. Other ratings available,
see Ordering Scheme.
Trip Free
Current Rating
Trip Indication
Auxiliary Switch Rating (optional) Integrated, load side.
SPST, 3A – 125VAC, 2A – 30VDC.
Auxiliary switch senses the on & off
position of circuit breaker handle,
as well as contact arm position.
Switch connections are screw
positively to the OFF position when
an overload causes the breaker to
trip. With mid-trip, the handle moves
to the mid position on electrical trip
of the circuit breaker. With mid trip
handle with alarm switch, handle
moves to the mid position and the
alarm switch actuates when the
circuit breaker is electrically tripped.
terminals.
Insulation Resistance
Dielectric Strength
Minimum of 100 Megohms at 500 VDC
UL, CSA: 1960 V 50/60 Hz for one
minute between all electrically
isolated terminals. G-Series circuit
breakers comply with the 8mm
spacing and 3750V 50/60 Hz dielectric
requirements from hazardous
voltage to operator accessible
surfaces, between adjacent poles
and from main circuits to auxiliary
circuits per Publications EN 60950
and VDE 0805.
Physical
Number of Poles
Weight
1 pole ≤ 63A, 2 poles ≤ 63A per pole
Approx.172 grams/pole ( 4.13 oz).
Housing: Black
Standard Colors
Environmental
Designed in accordance with requirements of specification
MIL-PRF-55629 & MIL-STD-202 as follows:
Shock
Withstands 100 Gs, 6ms sawtooth
while carrying rated current per
Method 213, Test Condition “I”.
Instantaneous and ultrashort curves
tested @ 90% of rated current.
Withstands 0.060” excursion from
10-55 Hz & 10 Gs 55-500 Hz, @
rated current per Method 204C, Test
Cond. A. Instantaneous & ultrashort
curves tested @ 90% of rated
current.
Method 106D, i.e., ten 24-hour
cycles @ +25°C to +65°C, 80-98% RH.
Method 101, Condition A (90-95%
RH @ 5% NaCl Solution, 96 hrs).
Method 107D, Condition A (five cycles
@ -55°C to +25°C to +85°C to +25°C).
Resistance, Impedance Values from Line to Load Terminal -
based on series trip circuit breaker.
RESISTANCE, IMPEDANCE VALUES
from Line to Load Terminals
(Values Based on Series Trip Circuit Breaker)
1000
Vibration
CURRENT
(AMPS)
TOLERANCE
(%)
100
10
0.10 - 5.0
5.1 - 20.0
20.1 - 63.0
15
25
35
O
H
M
S
1
Moisture Resistance
Salt Spray
0.1
0.01
Thermal Shock
0.001
0.01
0.1
1
10
100
Operating Temperature -40°C to +85°C
AMPERE RATING
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
|
4
G-Series Circuit Breaker - DIN Rail – UL Recognized – Ordering Scheme
G A 1 B 0 24 620 1 1 D C
8
9
10
Rating
11
Agency
Approval
1
2
3
4
5
6
7
Terminal
Actuator
Color &
Legend
Series
Actuator
Poles
Circuit
Aux/Alarm
Switch
Frequency
& Delay
Current Rating
1 SERIES
G
8 TERMINAL
1
Screw Terminal
2 ACTUATOR
9 ACTUATOR COLOR & LEGEND
A
S
Handle, one per pole
Actuator Color
White
I-O
A
C
F
H
K
M
P
ON-OFF
Dual
Legend Color
Black
Mid-Trip Handle, one per pole
B
D
G
J
1
2
3
4
5
6
7
8
Black
White
Red
White
Green
Blue
White
3 POLES
L
White
1
2
One
Two
3
4
Three
Four
Yellow
Gray
Orange
N
Q
S
Black
Black
R
Black
4 CIRCUIT
1
A
B
Switch Only (no coil)
Series Trip (current)
10 APPLICATION RATING
5
B
D
H
M
125 VDC
240 VAC
480 VAC
80 VDC
4
3
5 AUXILIARY / ALARM SWITCH
0
1
3
5
6
without Aux Switch
S.P.D.T., Screw Terminal
S.P.D.T. Screw Terminal (Gold Contacts)
Plug-in Terminal
Plug-in Terminal (Gold Contacts)
11 AGENCY APPROVAL
A
C
E
Without Approvals
UL Recognized, CSA Accepted
UL Recognized, CSA Accepted, TUV Certified, CCC Certified
6 FREQUENCY & DELAY
03 Switch Only
10 DC, Instantaneous
11 DC, Ultra Short
12 DC, Short
14 DC, Medium
16 DC, Long
20 50/60 Hz Instantaneous
21 50/60 Ultra Short
22 50/60 Hz Short
24 50/60 Hz Medium
Notes:
26 50/60 Hz Long
1
Switch only circuit only available when tied to a protected pole (Circuit code B)
- for .2 to 30 amps select current code 630
2
42 50/60 Hz High-inrush Short
44 50/60 Hz High-inrush Medium
46 50/60 Hz High-inrush Long
52 DC High-inrush Short
- for 31 to 50 amps select current code 650
- for 51 to 63 amps select current code 663
- Use delay 03 for all switch only poles
2
3
Hi Inrush Delays limited to 50A max
54 DC High-inrush Medium
56 DC High-inrush Long
On multi-pole breakers one auxiliary switch is supplied , mounted in the extreme
left pole when viewed from front of panel
480 VAC rating requires 3 or 4 pole break 3Φ and 2 pole break 1Φ
This construction is polarity sensitive when constructed as a single pole unit,
125 VDC is only available without agency approvals
4
5
7 CURRENT RATING (AMPERES)
CODE AMPERES
210 0.100
220 0.200
225 0.250
230 0.300
235 0.350
240 0.400
245 0.450
250 0.500
255 0.550
260 0.600
265 0.650
270 0.700
275 0.750
280 0.800
285 0.850
290 0.900
410 1.000
512 1.250
415 1.500
517 1.750
420 2.000
522 2.250
425 2.500
527 2.750
430 3.000
435 3.500
440 4.000
445 4.500
450 5.000
455 5.500
460 6.000
465 6.500
470 7.000
475 7.500
480 8.000
485 8.500
490 9.000
495 9.500
610 10.000
710 10.500
611 11.000
711 11.500
612 12.000
712 12.500
613 13.000
614 14.000
615 15.000
616 16.000
617 17.000
618 18.000
620 20.000
622 22.000
624 24.000
625 25.000
630 30.000
635 35.000
640 40.000
650 50.000
655 55.000
660 60.000
663 63.000
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
|
5
G-Series Circuit Breaker - DIN Rail – UL489 – Ordering Scheme
G A 1 B 0 24 620 1 1 D G
8
9
10
Rating
11
Agency
Approval
1
2
3
4
5
6
7
Terminal
Actuator
Color &
Legend
Series
Actuator
Poles
Circuit
Aux/Alarm
Switch
Frequency
& Delay
Current Rating
1 SERIES
G
8 TERMINAL
1
Screw Terminal
2 ACTUATOR
9 ACTUATOR COLOR & LEGEND
A
S
Handle, one per pole
Actuator Color
White
ON-OFF Dual
Legend Color
Black
1
Mid-Trip Handle, one per pole
B
D
G
J
1
2
3
4
5
6
7
8
Black
White
Red
White
Green
Blue
Yellow
Gray
White
3 POLES
L
White
1
2
3
One
N
Q
S
Black
Two
Black
Three
Orange
Black
4 CIRCUIT
B
Series Trip (current)
10 APPLICATION RATING
5
B
C
D
K
M
125 VDC
6
120/240 VAC
3
7
5 AUXILIARY / ALARM SWITCH
240 VAC
8
0
1
3
5
6
without Aux Switch
S.P.D.T., Screw Terminal
S.P.D.T. Screw Terminal (Gold Contacts)
Plug-in Terminal
Plug-in Terminal (Gold Contacts)
120 VAC
9
80 VDC
11 AGENCY APPROVAL
A
G
Without Approvals
UL489 Listed
6 FREQUENCY & DELAY
11 DC, Ultra Short
12 DC, Short
14 DC, Medium
16 DC, Long
21 50/60 Ultra Short
22 50/60 Hz Short
24 50/60 Hz Medium
26 50/60 Hz Long
4
42 50/60 Hz High-inrush Short
44 50/60 Hz High-inrush Medium
Notes:
4
1
2
3
Mid-trip Handle(s) available at 1 pole unit and 2 pole unit only.
Third pole of a 3 pole unit is switch only pole.
4
46 50/60 Hz High-inrush Long
4
On multi-pole breakers one auxiliary switch is supplied, mounted in the extreme left
pole when viewed from front of panel.
52 DC High-inrush Short
4
54 DC High-inrush Medium
4
5
6
Hi Inrush Delays limited to 50A maximum.
125VDC for 2 pole unit only.
4
56 DC High-inrush Long
120/240VAC for 2 pole and 3 pole unit only. Limited to 50A maximum, and third pole
of a 3-pole unit is switch only pole.
7
8
9
240VAC for 1 pole unit only, limited to 25A maximum
120VAC for 1 pole unit only, limited to 50A maximum.
80VDC for 1 pole unit only
7 CURRENT RATING (AMPERES)
CODE AMPERES
410 1.000
512 1.250
415 1.500
517 1.750
420 2.000
522 2.250
425 2.500
527 2.750
430 3.000
435 3.500
440 4.000
445 4.500
450 5.000
455 5.500
460 6.000
465 6.500
470 7.000
475 7.500
480 8.000
485 8.500
490 9.000
495 9.500
610 10.000
710 10.500
611 11.000
711 11.500
612 12.000
712 12.500
613 13.000
614 14.000
615 15.000
616 16.000
617 17.000
618 18.000
620 20.000
622 22.000
624 24.000
625 25.000
630 30.000
635 35.000
640 40.000
650 50.000
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
|
6
G-Series Circuit Breaker - DIN Rail - UL Recognized – Dimensional Specifications
Dimensional Specifications: in. [mm]
1 POLE WITHOUT AUXILIARY SWITCH
1 POLE WITH AUXILIARY SWITCH
(PLUG-IN TERMINAL BLOCK)
1 POLE WITH AUXILIARY SWITCH
(SCREW TERMINAL BLOCK)
MULTIPLE POLES WITH AUXILIARY SWITCH (PLUG-IN TERMINAL BLOCK)
Notes:
1
2
All dimensions are in inches [millimeters].
Tolerance ±.020 [.51] unless otherwise specified.
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
|
7
G-Series Circuit Breaker - DIN Rail - UL489 – Dimensional Specifications
Dimensional Specifications: in. [mm]
1 POLE WITH AUXILIARY SWITCH (PENDING)
1 POLE WITHOUT AUXILIARY SWITCH
(PLUG-IN TERMINAL BLOCK)
1 POLE WITH AUXILIARY SWITCH (PENDING)
(SCREW TERMINAL BLOCK)
MULTIPLE POLES WITH AUXILIARY SWITCH (PENDING) (PLUG-IN TERMINAL BLOCK)
Notes:
1
2
All dimensions are in inches [millimeters].
Tolerance ±.020 [.51] unless otherwise specified.
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
|
8
G-Series Circuit Breaker - DIN Rail – Mounting / Connector Specifications
UL RECOGNIZED
UL489
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
|
9
Sales Representatives, Distributors & Company Profile
Authorized Sales Representatives and Distributors
Click on a region of the map below to find your local representatives and distributors or visit
www.carlingtech.com/findarep.
CANADA
EUROPE
USA
MIDDLE
EAST
MEXICO
AFRICA
ASIA-PACIFIC
OCEANIA
SOUTH
AMERICA
About Carling
Founded in 1920, Carling Technologies is a leading manufacturer of electrical and electronic switches
and assemblies, circuit breakers, electronic controls, power distribution units, and multiplexed power
distribution systems. With four ISO registered manufacturing facilities and technical sales offices worldwide,
Carling Technologies Sales, Service and Engineering teams do much more than manufacture electrical
components, they engineer powerful solutions! To learn more about Carling please visit
www.carlingtech.com/company-profile.
To view all of Carling’s environmental, quality, health & safety certifications please visit
www.carlingtech.com/environmental-certifications
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
Worldwide Headquarters
Carling Technologies, Inc.
60 Johnson Avenue, Plainville, CT 06062
Phone: 860.793.9281 Fax: 860.793.9231
@
Email: sales carlingtech.com
@
Northern Region Sales Office: nrsm carlingtech.com
@
Southeast Region Sales Office: sersm carlingtech.com
@
Midwest Region Sales Office: mrsm carlingtech.com
@
West Region Sales Office: wrsm carlingtech.com
@
Latin America Sales Office: larsm carlingtech.com
Asia-Pacific Headquarters
Carling Technologies, Asia-Pacific Ltd.,
Suite 1607, 16/F Tower 2, The Gateway,
Harbour City, 25 Canton Road,
Tsimshatsui, Kowloon, Hong Kong
Phone: Int + 852-2737-2277 Fax: Int + 852-2736-9332
@
Email: sales carlingtech.com.hk
@
Shenzhen, China: shenzhen carlingtech.com
@
Shanghai, China: shanghai carlingtech.com
@
Pune, India: india carlingtech.com
@
Kaohsiung, Taiwan: taiwan carlingtech.com
@
Yokohama, Japan: japan carlingtech.com
|
|
Europe Middle East Africa Headquarters
Carling Technologies LTD
4 Airport Business Park, Exeter Airport,
Clyst Honiton, Exeter, Devon, EX5 2UL, UK
Phone: Int + 44 1392.364422 Fax: Int + 44 1392.364477
@
Email: ltd.sales carlingtech.com
@
Germany: gmbh carlingtech.com
@
France: sas carlingtech.com
www.carlingtech.com
REV_01_2019
相关型号:
GA2-B1-44-425-11-DE
Magnetic Circuit Breaker, 2 Pole(s), 2.5A, 240VAC, Din-rail Mount,
Carling Techn
©2020 ICPDF网 联系我们和版权申明